What Can a Drone Show During Tank and Piping Inspections?

Locate rust staining on elevated piping, document loose insulation jacketing on a tank, and compare repairs. Includes a sample scope for your next inspection.

INDUSTRIAL INSPECTIONS

Ahmed Hamada, API 510/570/653 Inspector & FAA Part 107 Pilot

11/19/20265 min read

AI-generated illustration of an industrial storage tank with exterior stairs and adjacent piping; not a client inspection.
AI-generated illustration of an industrial storage tank with exterior stairs and adjacent piping; not a client inspection.

A maintenance planner gets a sharp close-up of rust staining on elevated piping. Three lines cross that rack. There’s no line marker, support number, or wider view in the photo. The crew’s first question isn’t “How bad is it?” It’s “Which pipe are we going to?”

A regular color camera earns its place when the pictures change a work order. Which rack bays need access before the turnaround? Which floating roof warrants a closer look after rain? What will disappear when insulation goes back on? Here is what to request and where the visual evidence stops.

1. Before the turnaround, which elevated pipe-rack bays need access?

“Inspect the pipe rack” is too broad for a work order. A better question is: Which bays show open jacketing at the elbows, and which of those locations are hidden from the existing platform? Three elbows in the same frame can look identical once the image is cropped. Pair each detail with the rack column or bay reference, mark its position on the site-supplied drawing, and keep the unmarked original.

Use that record to identify locations for an access walkdown before the turnaround scope freezes. An open jacket is not proof of corrosion underneath it.

Start wide enough to show where the line runs through the rack. Then take a closer view that includes the stained area and a fixed reference, such as a numbered column or a recognizable elbow. If a line marker is legible, include it. If it isn’t, don’t guess the line number from the photo. Use the wider view to reconcile the location with the site team and its drawings.

Illustration: pipe-rack overview locates the support bay; the close-up shows rust-colored staining near the pipe-to-support contact.
Illustration: pipe-rack overview locates the support bay; the close-up shows rust-colored staining near the pipe-to-support contact.


Figure 1. Use the rack overview to locate the support bay, then read the close-up. AI-generated illustration; not a client inspection.

Sample photo log | Piping support (illustrative)
Location: Figure 1, left panel, foreground pipe at the yellow box above the green crossbeam. Line tag not readable.
Visible condition: Rust-colored staining on the lower side of the pipe beside the support.
Not visible: The contact surface between the pipe and the steel. The image does not establish wall loss.
Next action: Match the line and support bay to the site drawing during the walkdown. If the work order calls for remaining wall thickness, obtain the specified thickness reading.

2. After heavy rain, which floating roof needs attention first?

At a terminal with several external floating-roof tanks, a ground-level view may not show how much of each deck is obscured by standing liquid. An operator-approved view can put the roofs side by side: one has a patch beside the rolling ladder; another has an accumulation extending across several deck plates. That gives operations a reason to prioritize a particular tank for immediate review under its procedures.

Ask for one dated overview per tank, with the tank ID confirmed by the site, followed by a closer view that includes the patch and a fixed landmark. If a prior view exists, compare the same sector. Report what changed, not what caused it. A photograph does not identify the liquid, prove a drain is blocked, establish pontoon integrity, or clear the roof for access. The UK HSE floating-roof bulletin explains why rainfall and compromised buoyancy matter; it is not a drone inspection procedure. If site procedures call for immediate action, do not wait for a flight.

3. How far does loose insulation jacketing extend on the tank?

From grade, a lifted metal edge near a tank roof might look like a single loose panel. Before arranging access, the planner wants to know whether the adjacent panels are displaced too. Ask for a view that identifies the side of the tank, then one that shows the suspect seam, both neighboring panels, and a fixed landmark in the same frame. Add a detail of the exposed edge.

Example field note: “Immediately east of the top stair landing, one vertical jacketing edge stands away from the adjacent panel. The landing hides the lower end of the seam.” That tells the planner where to arrange closer access. It does not establish the condition of the steel beneath the insulation. Not seen is not the same as no damage found.

4. After maintenance, can we show what visibly changed?

Suppose the crew has resecured the jacketing. Ask for an after-view from the same side, with the same landing and seam in frame. Label the two views with the asset, location, and capture dates. Matching the landmark matters more than matching the zoom: two close-ups of similar metal panels don’t establish that the crew worked on the same one.

Illustration: tank insulation jacketing at the same stair landing before and after the loose panel edge was resecured.
Illustration: tank insulation jacketing at the same stair landing before and after the loose panel edge was resecured.


Figure 2. Compare the jacketing edge against the same stair landing in both views. AI-generated illustration; not a client inspection.

What belongs in the closeout note: “The edge that stood away from the panel in the earlier view now appears seated.” That documents the visible result. It doesn’t verify hidden fasteners, the seal behind the overlap, or work beneath the jacket.

5. Before insulation is closed up, what will the next crew wish it could see?

An overview taken after the last sheet of jacketing goes back on cannot show what was underneath. On a rack refurbishment, the useful time for a visual record may be between removal and reinstatement, after the site releases the area for photography. Pair the bay overview with the exposed location while it is visible; take the matching overview again after reinstatement. Link both to the work order and the inspector’s separate examination record.

Months later, a planner can find which elbow was exposed and which adjacent run was outside the work. The photos do not replace the inspector’s hold-point release or the recorded measurements. And if the inspector already has safe access and can take a better detail photo by hand, use the drone only for the overview, or leave it on the ground.

6. Has nearby excavation changed conditions at a pipeline crossing?

A contractor is opening a trench near an operator-identified crossing. The owner asks, “Has the work moved closer to the crossing since last week, and where should our field representative meet the crew?” A tight photograph of an excavator won’t answer either question. Request a dated overview from the same approved viewpoint on both visits. Keep the access road, a fixed landmark and the visible limits of ground disturbance in frame.

Deliver the two originals and a marked copy keyed to the operator’s crossing reference. A useful log entry reads: “Newly disturbed ground is visible between the access road and the east fence corner; the earlier image shows undisturbed ground there.” That gives the operator a specific location to check. It does not locate buried pipe, measure clearance, replace utility locating, or authorize digging. For industry context, see PHMSA’s response to Shell about aerial right-of-way imagery.

A scope request you can copy

“Document the upper east side of Tank T-101, starting at the top stair landing. Show whether the displaced insulation jacketing continues onto adjacent panels. Provide an orientation photo, labeled detail views, and a note identifying any area that could not be seen.”

Before booking, add the site’s flight and photography restrictions, the detail you need to see, and who will review the result. If the detail can’t be resolved from an approved position, record that limitation rather than marking the area complete.

About the author: Ahmed Hamada is an API 510, 570 and 653 certified inspector and FAA Part 107 remote pilot based in Katy, Texas.

Planning a tank or piping inspection in Greater Houston? Send Everest Drone the asset, the location, and the question your crew needs answered. We’ll discuss whether a visual flight can answer it. You can also review our industrial drone inspection scope and deliverables.